DH+ Network Transfers

You need one of the following Allen-Bradley Data Highway Plus
(DH+) interface modules installed in the development computer to
transfer applications over a DH+ network:

1770-KF2/1785-KE

1784-KL

1784-KT

1784-KT2

1784-KTK1

1784-PCMK

1784-KTX

You can transfer applications over a DH+ network using RSLinx
drivers, or Serial 1 or Serial 2 drivers if the transfer is over a KF2
module.

To download over a DH+ network, the development computer and
PanelView terminal can be on the same network or on two different
bridged DH+ networks.

File transfers over one ControlLogix bridge can be supported. You
can transfer files from the development computer over a DH+,
ControlNet, or Ethernet network to a ControlLogix gateway module,
and then bridged to the PanelView terminal over a DH+ or
ControlNet network. ControlLogix gateway modules are:
1756 DH/RIO, 1756 CNB, and 1756 ENET.