3–2

Uploading 1000e/1200e/1400e Application Files and Alarm History Files

To prepare the PanelView terminal for a serial upload:

1. Using the hardware keyswitch or the Goto Configure Mode

button, switch the PanelView terminal to the Configure mode.

2. In the Terminal Configuration screen, choose the Transfer Setup

button to display the Transfer Setup screen.

3. To change the settings, choose the Baud Rate, Parity, or Error

buttons to move the check mark to the setting you want.

Baud Rate

ĊThe speed at which data is transmitted over the

serial cable. The default setting for a serial transfer is
9600 baud.

Parity

ĊUsed to check for accurate transmission of the data

between the development computer and terminal. The default
setting is None.

Error

ĊUsed to check for errors in the data transmission.

Error transmission is either

CRC

Ċcyclical (or cyclic) redundancy check.

BCC

Ċblock check character. BCC is the default setting.

The settings that are defined in the Transfer Setup screen must
match the Transfer Utility’s settings.

4. When you have selected the required settings, choose OK to exit

this screen.