6–9

Troubleshooting for the PanelView e Transfer Utility 32

Use the following table to identify Transfer Utility problems you
may encounter due to driver selection.

Problem

Cause

What to do

The Rockwell Software RSLinx communication
software is not currently running.
This software package is required in order to
perform file transfers.
(Error 4300)

RSLinx communication software is not
installed.

Install RSLinx.

The selected driver is a Rockwell Software
RSLinx network driver.
Use the RSLinx software package in order to
configure the communication network driver.
(Error 4331)

The driver in RSLinx is not configured.

Use the RSLinx communication software to
configure the driver.

Incorrect routing address could corrupt data in a
non-PanelView device.
Verify the correct address has been specified.
Do you want to continue?
(Warning 4332)

This will occur for network and Remote I/O
transfers. The routing address may be
incorrect.

Check that the address is correct. Choose
Yes to continue. Choose No to cancel.

The driver is not properly configured.
Check whether RSLinx is installed or how the

The third-party RSLinx communication
package may not be installed.

Install RSLinx.

driver is configured.
(Error 4333)

The RSLinx driver used for the transfer may
not be configured properly.

Use the RSLinx communication software to
configure the driver.

No selection was made from the Station
Browser.
(Error 4340)

A device was not selected in Station
Browse.

Select a device in Station Browse, or press
Cancel.

The selection must be a Pass-Through device
(e.g. PLC or ControlLogix RIO Module) for RIO
Pass-Through transfers.
(Error 4341)

An invalid device was selected.

Select a Pass-Through device, or press
Cancel.

The selection must be a PanelView terminal for
network transfers.
(Error 4342)

An invalid device was selected.

Select a PanelView terminal, or press
Cancel.

Consult the following table to identify and respond to some common
error messages that can appear on the screen when you upload or
download data, or upload Alarm History files.

Message

Cause

What to do

БББББББББББББ

БББББББББББББ

Data received too fast from PanelView terminal.

БББББББББББ

БББББББББББ

Upload speed too high.

БББББББББББ

БББББББББББ

Reduce baud rate.

БББББББББББББ

БББББББББББББ

Б ББББББББББББ

БББББББББББББ

Invalid baud.

БББББББББББ

БББББББББББ

Б ББББББББББ

БББББББББББ

Might not be accessing COM port.

БББББББББББ

БББББББББББ

Б ББББББББББ

БББББББББББ

Check other program or devices that use
the COM port.

If there is one, check to see that the internal
modem is turned off.

БББББББББББББ

БББББББББББББ

No response from PanelView terminal.

БББББББББББ

БББББББББББ

Baud rate too high.

БББББББББББ

БББББББББББ

Reduce baud rate.

БББББББББББББ

БББББББББББББ

БББББББББББББ

БББББББББББ

БББББББББББ

БББББББББББ

Other possible causes are the same as the
items marked in the previous table.

БББББББББББ

БББББББББББ

БББББББББББ

See solutions for items marked in the
previous table.

БББББББББББББ

БББББББББББББ

БББББББББББ

БББББББББББ

Possible corrupt application file.

БББББББББББ

БББББББББББ

Try backup file or demo file.

Serial cable becomes disconnected during
a serial download.

Ensure the serial cable is properly
connected, and try the download again.

Driver Errors

PanelView 1400e Transfer
Utility Error Messages FTU
Version 3