Downloading 1000e/1200e/1400e Application Files

To prepare the PanelView terminal for a network download:

1. To use the Current Application’s transfer parameters, make sure

the PanelView terminal is in Run mode to start running the
application, and then follow the next procedure to configure the
PanelView e Transfer Utility 32 for the download. A Current
Application is a file that is currently selected and running on the
PanelView terminal.

To view the Current Application’s transfer parameters, switch the
PanelView terminal to Configure mode. At the PanelView
terminal, choose the Terminal Network Setup button in the
Terminal Configuration screen to display the Terminal Network
Setup screen. Exit the screen after you finish viewing the transfer
parameters. Go to step 7.

To download with transfer parameters different from those of the
Current Application or if you don’t have a Current Application
selected, switch the PanelView terminal to Configure mode. At
the PanelView terminal, choose the Transfer Setup button. Go to
step 2.

2. Select the Network tab.

3. Choose Network Direct as the Address Source. When you choose

Network Direct, the configuration parameters from the
application file are disabled.

4. Select DH+ or ControlNet as the network type.