Ftu32 ver 5 communication errors – Rockwell Automation 2711E-ND7 PanelView File Transfer Utility User Manual User Manual

Page 91

Advertising
background image

6–3

Troubleshooting for the PanelView e Transfer Utility 32

Use the following table to identify communication problems you
may encounter.

Problem

Cause

What to do

БББББББББББББ

БББББББББББББ

БББББББББББББ

Cannot start any transfer command. Channel is
busy.
(Error 2103)

БББББББББББ

БББББББББББ

БББББББББББ

The PanelView terminal may currently be
busy.

БББББББББББ

БББББББББББ

БББББББББББ

Wait for the PanelView terminal to complete
its current process, and try again.

БББББББББББББ

БББББББББББББ

БББББББББББББ

File was not found.
(Error 2112)

БББББББББББ

БББББББББББ

БББББББББББ

The specified download application file
cannot be read.

БББББББББББ

БББББББББББ

БББББББББББ

Ensure the specified download application
file exists and is not corrupted.

БББББББББББББ

БББББББББББББ

БББББББББББББ

Could not create specified upload file.
(Error 2113)

БББББББББББ

БББББББББББ

БББББББББББ

The specified upload application file cannot
be written.

БББББББББББ

БББББББББББ

БББББББББББ

Ensure the directory exists, and there is
enough disk space.

БББББББББББББ

БББББББББББББ

No current application file exists.
(Error 2114)

БББББББББББ

БББББББББББ

There is no current application selected in
the PanelView terminal.

БББББББББББ

БББББББББББ

Ensure a current application is selected in
the terminal.

БББББББББББББ

БББББББББББББ

БББББББББББББ

Could not read data from download file.
(Error 2115)

БББББББББББ

БББББББББББ

БББББББББББ

The specified download application file
cannot be read.

БББББББББББ

БББББББББББ

БББББББББББ

Ensure the specified download application
file exists and is not corrupted.

БББББББББББББ

БББББББББББББ

Б ББББББББББББ

Б ББББББББББББ

БББББББББББББ

It is now too late to abort the file transfer.
(Warning 2117)

БББББББББББ

БББББББББББ

Б ББББББББББ

Б ББББББББББ

БББББББББББ

All packets are sent; you cannot cancel the
file transfer at this point.

БББББББББББ

БББББББББББ

Б ББББББББББ

Б ББББББББББ

БББББББББББ

If you want to delete the transferred
application, start the file transfer again with
the same application. Immediately cancel
the file transfer. The second file transfer
overwrites the first file transfer.

Bad communication, PV missed a download
packet.
(Error 2118)

There may be an unrecoverable error.

Exit and run the program again.

Could not write data to the upload file.
(Error 2119)

The specified upload application file cannot
be written.

Choose another drive that has available
disk space, or free up some space on the
disk drive that is full.

The destination drive has insufficient free space
to perform the requested operation. Free up
some disk space on the target drive and try
again.
(Error 2120)

The destination drive has insufficient free
disk space.

Choose another drive that has available
disk space, or free up some space on the
disk drive that is full.

PLC Inhibit bit is set.
(Error 3101)

The application that is currently running in
the PanelView terminal may be inhibiting file
transfers.

Check the PLC inhibit bit. Reset the bit if
you want to continue with the transfer.

The selected terminal storage is out of space for
the download application.
Do you want to select another terminal storage?
(Warning 3103)

The selected terminal storage area has
insufficient storage space in the PanelView
terminal.

Choose Yes to select another terminal
storage area. Choose No to cancel the
download.

PCMCIA card ejected.
(Error 3108)

The card is ejected from the PanelView
terminal.

Insert the PCMCIA card into the PanelView
terminal, or select another terminal storage
area. Then try the transfer again.

The download file already exists on the
PanelView terminal. Do you want to overwrite it
on the PanelView terminal?
(Warning 3111)

An application with the same name may
already exist in the PanelView terminal.

Choose Yes to overwrite the download file
on the PanelView terminal. Choose No to
cancel the file transfer.

PCMCIA card is write protected.
(Error 3114)

The card is write protected.

Disable write protection. Or, select another
storage area.

Alarm History is empty, therefore, no file was
uploaded.
(Warning 3120)

You cannot upload an empty alarm history
file.

Wait for alarm entries in the alarm history
file.

The download file already exists on the
PanelView terminal.
Do you want to overwrite it on the PanelView
terminal and make the application current?
(Warning 3121)

Either an application with an identical name
already exists in the PanelView terminal, or
there is not enough space, or you did not
choose to make the application current.

Choose Yes to overwrite the application file
on the PanelView terminal and make the
application current. Choose No to cancel
the file transfer.

FTU32 Ver 5
Communication Errors