Rockwell Automation 2711E-ND7 PanelView File Transfer Utility User Manual User Manual

Page 95

Advertising
background image

6–7

Troubleshooting for the PanelView e Transfer Utility 32

Problem

What to do

Cause

Host PC failed to communicate with PanelView
terminal. Error code RDM number: 0x%X
(Error 4209 continued)

For Remote I/O Pass-Through transfers:
The specified transfer path may be incorrect
for the target Pass-Through device.

Check the Pass-Through device for its
address. Ensure it matches the Transfer
Utility’s transfer path.

For Remote I/O Pass-Through transfers:
The wrong development computer network
driver may be used or incorrectly
configured.

Ensure the correct network driver is used,
and use the communication software to
configure the network driver.

For Remote I/O Pass-Through transfers:
The terminal is incorrectly in the Configure
mode; it must be in Run mode.

Switch the PanelView terminal to Run
mode.

No KTCx card found on PanelView terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4211)

A required KTCx card is not installed in the
PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

No serial card found on PanelView terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4212)

A required serial card is not installed in the
PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

No KTCs card found on PanelView terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4213)

A required KTCs card is not installed in the
PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

The KTCs driver cannot be used with a KTCs
card and the KTCs driver cannot be used with a
KTCx card.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4215)

The driver and the card do not match. The
KTCx driver requires the KTCx card, and
the KTCs driver requires the KTCs card.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

The application to be downloaded:
%s (%s)
is not newer than the current application in the
terminal:
%s (%s)
Do you want to continue?
(Warning 4221)

The download application is not newer than
the one currently running in the PanelView
terminal.

Choose Yes to continue. Choose No to
cancel the file transfer.

PanelView terminal has an earlier version %s
than the download application’s %s targeted
version %s and up.
The application cannot be made current after
download.
Do you want to continue?
(Warning 4222)

The PanelView terminal is running an
earlier firmware version that does not
support the download application’s targeted
firmware version.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

The application %s network type %s is not
supported for this version’s %s PanelView
terminal.
The download application cannot be made
current after download.
Do you want to continue?
(Warning 4223)

The download application’s network type is
not supported by the PanelView terminal’s
firmware.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.