Compatibility errors – Rockwell Automation 2711E-ND7 PanelView File Transfer Utility User Manual User Manual

Page 93

Advertising
background image

6–5

Troubleshooting for the PanelView e Transfer Utility 32

Problem

What to do

Cause

Unable to read application header details from
the PVD file “%s”.
This file may be corrupt or incorrectly used.
(Error 4126)

The runtime application may be corrupt.

Ensure your file is a *.pvd file and that it is
not corrupted.

Unable to read file transfer details from the PVD
file “%s”.
This file may be corrupt or incorrectly used.
(Error 4127)

The runtime application may be corrupt.

Ensure your file is a *.pvd file and that it is
not corrupted.

The upload destination directory is blank.
Enter a valid upload directory path.
(Error 4128)

You must specify a directory to upload to.

Enter an upload destination or press
Browse to search for one, and try again.

Some of the alarms may not be acknowledged.
Do you still want to clear the uploaded alarms
from the terminal’s Alarm History screen?
(Warning 4130)

You have chosen to clear the alarms in the
alarm history after uploading.

Choose Yes to clear the alarms. Choose No
to not clear the alarms.

The transfer parameters in the application file to
be downloaded are invalid.
(Error 4131)

The transfer method is Application, and the
file that you are downloading does not have
the transfer parameters set up properly.

Load the .pvd file in PanelBuilder. Check
that the transfer parameters are set up
properly in PanelBuilder, for example, the
Pass-Through Control Byte has been
defined.

Use the following table to identify Transfer Utility problems you
may encounter due to incompatibility between the *.pvd file and the
PanelView terminal.

Problem

Cause

What to do

Transfer inhibit bit is set.
(Error 4200)

The application that is running on the
PanelView terminal may be inhibiting file
transfers.

Check the PLC inhibit bit and reset the bit.

No Remote I/O driver found on PanelView
terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4201)

A required Remote I/O driver is not installed
in the PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

No DH+ driver found on PanelView terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4202)

A required DH+ driver is not installed in the
PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

No ControlNet (KTCx) driver found on PanelView
terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4203)

A required ControlNet Unscheduled driver is
not installed in the PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

No Modbus driver found on PanelView terminal.
The download application cannot be made
current when download completes.
Do you want to continue?
(Warning 4204)

A required Modbus driver is not installed in
the PanelView terminal.

Choose Yes to continue. Choose No to
cancel the file transfer. The application will
not be selected.

Compatibility Errors