2 data processing time, Data proc, Data processing time -3 – KEYENCE CB-EP100 User Manual

Page 115: Data processing time

Advertising
background image

4-3

4

Sp
ec
ific

a

tio

ns

- EtherNet/IP Network Unit CB-EP100 User’s Manual (LJ-V7000 Edition) -

4-2

Data Processing Time

This section describes the length of time that lasts from detection by a sensor to data
processing by PLC.

Maximum data processing time = (1) + (2) + (3) + (4)
(1) PLC scan time
(2) RPI (Transmission cycle)
(3) CB-EP100 data communication time
(4) Measuring instrument response time

(2) RPI is set with the scanner unit. It can be set in 0.5 ms increments between 0.5 ms

and 10000 ms.

(3) Maximum data communication delay times for CB-EP100

Maximum data transfer delay time from the CB-EP100 to a measuring instrument: 1 ms
Maximum data transfer delay time from a measuring instrument to the CB-EP100: 6 ms

For details of times for (4) above, refer to the User's Manual of the measuring
instrument.

CPU unit

EtherNet/IP

scanner

CB-EP100

Measuring instrument

(1)

(2)

(3)

(4)