- EtherNet/IP Network Unit CB-EP100 User’s Manual (LJ-V7000 Edition) -

3-4 Message Communication

3-30

3

Communi

cat

in

g wit

h the

L

J

-V700

0 Ser

ies

(2) Writing setting values to a measuring instrument

Message communication writes parameters to the a measuring instrument.
In the following example, the offset of OUT1 is changed from 5000 to 6000.

"(2) Writing setting values to a measuring instrument" (Page 3-75)

(3) Changing programs

Message communication acquires measurement values from a measuring
instrument connected to the CB-EP100.
In the following example, the program number is set to 9.

"(3) Changing programs" (Page 3-76)

(4) Clearing an error

Message communication clears a recoverable error occurring on the CB-EP100 or
a measuring instrument connected to the CB-EP100.

"(4) Clearing errors" (Page 3-77)

Command:
6000

Response

Current program No. 3 OUT1
offset value for a measuring
instrument: 6000

CB-EP100

Scanner

<Details of command>
Service code: 10H
Class ID: 6BH
Instance ID: 203(CBH)
Attribute ID: 2456(998H)
Service data: 6000

Measuring
instrument

Command: 09H

Response

The program number of the measuring
instrument becomes 9.

CB-EP100

Scanner

<Details of command>
Service code: 4BH
Class ID: 6BH
Instance ID: 01H
Attribute ID: None
Service data: 0000 0009H

Measuring
instrument

Command

Response

CB-EP100

Scanner

<Details of command>
Service code: 4CH
Class ID: 6BH
Instance ID: 00H/01H
Service data: None

Measuring
instrument

The error is cleared and
operation is resumed.