5-4 Configuration Procedure for Control/Compact Logix Series

5-7

5

Ap
pe
ndi

x

- EtherNet/IP Network Unit CB-EP100 User’s Manual (LJ-V7000 Edition) -

(1) Name

Any setting

(2) Comm Format

Any setting

*1

(3) IP Address

IP address setting of CB-EP100

(4) Input (Assembly Instance)

100 (fixed)

(5) Input (Size)

Input assembly size setting of CB-EP100

*4

(6) Output (Assembly Instance)

101

*2

(7) Output (Size)

Output assembly size setting of CB-EP100

*2*4

(8) Configuration

1

*3

(9) Configuration Size

0

*3

*1

This can be set to anything, but programming will be easier if you set a format
that allows 4-byte alignment on the assembly object structure.
When connecting with Exclusive Owner, use Data-DINT.
When connecting with Input Only, use with Input Data-DINT.

*2

To perform operation with Input Only, set (6) to 254 and (7) to 0.

*3

Configuration is not used with CB-EP100, but input the value above because
an error occurs if nothing is input.

*4

The assembly size of Input is set in 8-bit (1-byte increments) for CB-EP100, but
it is set in 32-bit (4-byte increments) in RSLogix5000.
Set the assembly size of Input and assembly size of Output for CB-EP100 to
values higher than those of (5) and (7), respectively.

(1)

(2)

(3)

(4)

(5)
(7)
(9)

(6)

(8)