- EtherNet/IP Network Unit CB-EP100 User’s Manual (LJ-V7000 Edition) -

2-3 Wiring

2-6

2

Con

nect

io

n a

nd

Conf

ig

urat

io

n

„

CB-EP100 connector port

The CB-EP100 connector port accepts an RJ-45 8-pole modular connector (ISO8877
compliant) used with 10BASE-T and 100BASE-TX and complies with the IEEE802.3
Standards.

Precautions for connecting a STP/UTP cable to the CB-EP100 connector port
Take care not to apply a load to the CB-EP100 connector port when connecting the
STP/UTP cable to the CB-EP100.

„

Connecting the CB-EP100 to EtherNet/IP

The following describes how to connect the CB-EP100 to the RJ-45 connector.

1

Turn off the power supply.

2

Connect one modular jack of the STP/UTP cable to the 10BASE-T/

100BASE-TX port of the Ethernet switch to be used.

Insert the modular jack until a "click" is heard. The modular jack and connector
will lock.

Keep the length of the STP/UTP cable to be used 100 m or less.
Carefully check the shape and type of connector (port) on the

Ethernet switch before connecting the CB-EP100 to the Ethernet
switch.

3

Connect the modular jack on the other end of the STP/UTP cable to the

CB-EP100 connector port.

Insert the jack until a "click" is heard. The modular jack and connector will lock.

The cable may be bent and used when installed. Bending the cable

at a sharp angle may cut the wires in the cable or the cable may be

disconnected during use. Install or lay the cable to be used with

attention to the recommended bending radius R of the cable.