E1 v/f pattern, E1-01 input voltage setting, E1-03 v/f pattern selection – Yaskawa iQpump Drive User Manual User Manual

Page 105

Advertising
background image

5.1 iQpump Basic Programming Parameters

YASKAWA TM.iQp.01 iQpump Drive User Manual

105

E1 V/f Pattern

E1-01 Input Voltage Setting

Setting Range: 155.0 V to 255.0 V (208 V/240 V Models)

310.0 V to 510.0 V (480 V Models)

Factory Defaults: 208.0 V (208 V Models)

240.0 V (240 V Models)

480.0 V (480 V Models)

Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the levels of

some protective features of the iQpump drive (i.e. Overvoltage, Stall Prevention, etc.). E1-01 also serves as the Maximum/Base Voltage

used by the Preset V/Hz curves (E1-03 = 0 to D).

E1-03 V/f Pattern Selection

Table 5.2

The iQpump drive operates utilizing a set V/f pattern to determine the appropriate output voltage level for each commanded speed. There

are 14 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum voltage is

reached), and maximum frequencies.

There are also settings for Custom V/f patterns that will allow the programmer to manually set (“Customize”) the V/f pattern using

parameters E1-04 through E1-13.

Using parameter E1-03, the programmer can select one of the preset V/f patterns or chose between a custom V/F pattern with an upper
voltage limit (E1-03 = “F: Custom V/F”) and a custom V/f pattern without a voltage limit (E1-03 = “FF: Custom w/o limit”).

Setting

Description

0

50 Hz

1

60 Hz Saturation

2

50 Hz Saturation

3

72 Hz

4

50 Hz VT1

5

50 Hz VT2

6

60 Hz VT1

7

60 Hz VT2

8

50 Hz HST1

9

50 Hz HST2

A

60 Hz HST1

B

60 Hz HST2

C

90 Hz

D

120 Hz

E

180 Hz (invalid - OPE2 fault will occur)

F

Custom V/f (factory default, with parameter values per setting 1)

FF

Custom w/o limit