4.6 Low Feedback Level Alarm and Fault Setup

80

YASKAWA TM.iQp.01 iQpump Drive User Manual

Figure 4.5 Low Feedback Timing Chart

Example: Constant Pressure System

System Units set to PSI (P1-02 = PSI)

System Setpoint set for 80 PSI

Pressure Transducer: 150 PSI

Desired Operation:

Pump System should show low feedback alarm when feedback level falls below 50 PSI and fault the system if the feedback level

stays there for more than 30 sec.

Solution: Program P1-07 to 50 PSI and P1-08 to 30 sec.

Note: Low feedback detection is only active during running in Auto Mode.