E1-04

0303H

Maximum Output
Frequency
Max Frequency

To set V/f characteristics in a straight line, set the same values for E1-07
and E1-09. In this case, the setting for E1-08 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E1-04 (FMAX) ˜ E1-06 (FA) > E1-07 (FB) ˜ E1-09 (FMIN)

0.0 to

120.0 Hz

60.0 Hz Programming

41

E1-05

0304H

Maximum Output
Voltage
Max Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

230.0 V

460.0 V

Programming

41

E1-06

0305H

Base Frequency
Base Frequency

0.0 to
200.0

60.0 Hz Programming

42

E1-07

0306H

Mid Output Frequency A
Mid Frequency A

0.0 to
200.0

3.0 Hz

Programming

42

E1-08

0307H

Mid Output Voltage A
Mid Voltage A

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

17.2 VAC
34.5 VAC

Programming

42

E1-09

0308H

Minimum Output
Frequency
Min Frequency

0.0 to
200.0

1.5 Hz

Programming

42

E1-10

0309H

Mid Output Voltage
Min Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

10.3 VAC
20.7 VAC

Programming

42

E1-11

030AH

Mid Output Frequency B
Mid Frequency B

Set only when V/f is finely adjusted at rated output range.
Adjustment is not normally required.

0.0 to
200.0

0.0 Hz

Programming

42

E1-12

030BH

Mid Output Voltage B
Mid Voltage B

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

0.0 VAC Programming

42

E1-13

030CH

Base Voltage
Base Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

0.0 VAC Programming

42

Motor Setup

E2-01

030EH

Motor Rated Current
Motor Rated FLA

Set to the motor nameplate full load amps.

10% to

200%

kVA

Dependent

Pump Quick

Setup

45

E2-03

030FH

No-Load Current

Sets the magnetizing current of the motor.

kVA

Dependent

kVA

Dependent

Programming

45

E2-04

0311H

Number of Motor Poles
Number of Poles

Set to the number of poles. Used for no-flow detection function and for
the calculation of RPM related parameters.

2 to 48

2

Pump Quick

Setup

45

E2-05

0312H

Motor Line-to-Line
Resistance
Term Resistance

Phase to phase motor resistance, normally set by the autotuning
routine.

0.000 to

65.000

kVA

Dependent

Programming

45

Com OPT Setup

F6-01

03A2H

Operation Selection after
Communication Error
Com Bus Flt Sel

Sets the stopping method for option PCB communications error (BUS
fault). Active only when a communications option PCB is installed and
when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

1

Programming

46

F6-02

03A3H

Input Level of External
Fault from
Communication Option
Card
EF0 Detection

0: Always detected
1: Detected only during run

0 or 1

0

Programming

46

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

Output voltage (V)

Frequency (Hz)

FMIN FA FBASE FMAX

(E1-09) (E1-07) (E1-06) (E1-04)

VMAX
(E1-05)
VBASE
(E1-13)

VA
(E1-08)

VMIN
(E1-10)

Advertising