2 iqpump keypad messages, Iqpump keypad messages, Pump fault and alarm messages – Yaskawa iQpump Drive User Manual User Manual

Page 141

Advertising
background image

6.2 iQpump Keypad Messages

YASKAWA TM.iQp.01 iQpump Drive User Manual

141

6.2

iQpump Keypad Messages

Pump Fault and Alarm Messages

The iQpump has a comprehensive set of dedicated pump alarms and faults that will alert the operator when the pump system has

experienced any problems. A warning or fault message on the operator display indicates abnormal iQpump drive status.

Pump Fault Messages Generated

Table 6.2 Pump Fault Messages Generated

Digital Operator

Display

Description

Cause

Corrective Action

EF1-7

Pump Fault S#

External Pump Fault

Digital input is closed.

Check incoming digital signal from

external device.

FBL

Feedback Loss

<0032>

PI Feedback Loss

This fault occurs when PI
Feedback Loss Detection is
programmed to fault (b5-12

= 2) and the PI Feedback <
PI Feedback Loss Detection
Level (b5-13) for the PI

Feedback Loss Detection
Time (b5-14).

PI Feedback source (e.g. transducer, sensor,
building automation signal) is not installed

correctly or is not working.

Verify iQpump is programmed to
receive the PI Feedback source signal.

Check to ensure the PI Feedback

source is installed and working
properly.

HFB

High Feedback

High Feedback Fault

Feedback signal is too high.

The feedback level has risen above P1-09 level for
the time specified in P1-10. High feedback fault is

active in Hand Mode, Auto Mode, Pre-charge and
Thrust Mode when the Drive is running.

Feedback level lower than the high

feedback level (P1-09).

LFB/LW

Low FB / Water

Low Feedback Level Fault

Feedback signal is too low or
water low input closed.

The feedback level has dropped below P1-07 for

the time specified in P1-08 or water low input is
active. Low feedback fault is active in Auto Mode
when the iQpump is running. Digital input is
closed.

Feedback level greater than the low
feedback level (P1-07). Check

incoming digital signal from external
device.

LOP

Loss of Prime

<0032>

Loss of Prime Fault

Pump has lost its prime.

If the output current drops below the P1-14 Prime
Loss Level for the time specified in P1-12 and the

output frequency is at fmax, a “Loss of Prime
(LOP)” fault occurs

Possible cause: Dry Well, Air in System, No Water

Allow system to pump water again

(must have resistance in pump).

NMS

Set Point Not Met

<0032>

Not Maintaining Set Point
Fault

Set Point cannot be

maintained.

When the setpoint cannot be maintained for a time
specified in P1-12, a “Not Maintaining Setpoint

(NMS)” fault occurs. The function is disabled
when the drive is not running and the PID is not
active.

Possible cause: Blocked Impeller, Over-Cycling,

Broken Pipe

Reduce the difference between the

setpoint and the feedback smaller than
the Maximum Setpoint Difference
(P1-11).

OPE12

<0032>

Thermostat Fault Selection

Fault

Both Normally Open (H1-xx-= 83) and the
Normally Closed (H1-xx = 87) Thermostat Fault
inputs have been programmed

Only use one of the two fault inputs.

Advertising