6.5 Auto-Tuning Faults

YASKAWA TM.iQp.01 iQpump Drive User Manual

147

6.5

Auto-Tuning Faults

Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor

coasts to a stop during operation. The fault contact is not activated.

Table 6.5 Auto-Tuning Displays and Processing

Digital Operator Display

Probable Cause

Corrective Action

Er - 01

Fault

• There is an error in the data input for autotuning.
• There is an error in the relationship between the motor

output and the motor rated current.

• Check input data.
• Check iQpump and motor capacity.

• Check motor rated current.

Er - 02

Minor Fault

A minor fault is detected during auto-tuning.

• Check input data.
• Check wirings and around the machine.

• Check the load.

Er - 03

STOP key

The STOP key is pressed during auto-tuning, and the auto-
tuning is interrupted.

Er - 04

Resistance

Auto-tuning is not completed within the specified time.

The auto-tuning result became other than the parameter set
range.

• Check input data.
• Check motor wiring.
• If a motor and a machine are connected, disconnect the

motor from the machine.

Er - 12

I-det. Circuit

• Current flow exceeded the motor rated current.
• Current detection value symbol was reversed.

• Any of U/TI, V/T2, and W/T3 has open-phase.

• Check current detection circuit, wiring and mounting

procedure.

Er - 13

Leakage Inductance Fault

Auto-tuning did not finish within the set time.

Tuning result was outside the acceptable parameter setting
range.

• Check motor wiring.

End - 3

Data Invalid

Rated current set value is set too high.

• Check input data (especially, motor output current and

motor rated current value).

Advertising