2 preventive maintenance, Preventive maintenance – Yaskawa iQpump Drive User Manual User Manual

Page 161

Advertising
background image

7.2 Preventive Maintenance

YASKAWA TM.iQp.01 iQpump Drive User Manual

161

7.2

Preventive Maintenance

Table 7.3 Preventive Maintenance

If the iQpump drive is used under the following conditions, it may be necessary to inspect more often:

• High ambient temperatures, humidity or altitudes above 3,300 feet
• Frequent starting and stopping

• Fluctuations of the AC power supply or load

• Excessive vibration and/or shock loading
• Poor environment, including dust, metal particles, salt, sulfuric acid, chlorine

Inspection Points

Item

Check Points

Every 3-6

Months

Yearly

General

Environment

Ambient Temperature

Humidity

Dust

Harmful Gas

Oil Mist

X

X

X

X

X

Equipment

Abnormal vibration or noise

X

AC Power Supply

Main circuit & control voltage

X

AC Power Circuit &

Devices

Conductors & Wire

Connections

Loose lugs, screws & wires

Hot spots on parts

Corrosion

Bent conductors

Breakage, cracking or discoloration

Check spacing

X

X

X

X

X

X

Transformers & Reactors

Discoloration or Noise

X

Terminal Blocks

Loose, damaged

X

DC Bus Capacitors

Leakage

Ruptures, broken, expansion

Capacitance & insulation resistance

X

X

X

Relays & Contactors

Noisy

Contact discoloration

X

X

Soft Charge Resistors

Cracked

Discoloration

X

X

Control Circuits

Operation

Speed reference voltage/current

I/O contact operation

X

X

Cooling System

Cooling Fans/Fins & Heatsink

Abnormal fan noise

Loose connectors

Free of accumulation

X

X

X

Keypad/Diplay

Digital Operator

LEDs

Monitor display values

Key functionality

Clean

X

X

X

X

Advertising