7.1 Periodic Inspection

160

YASKAWA TM.iQp.01 iQpump Drive User Manual

7.1

Periodic Inspection

Check the following items during periodic maintenance.

• The motor should not be vibrating or making unusual noises.

• There should be no abnormal heat generation from the iQpump drive or motor.
• The ambient temperature should be within the iQpump drive specification of -10

°C to 40°C (14°F to 104°F).

• The output current value shown in parameter U1-03 should not be higher than the motor rated current for an extended period of time.

• The cooling fan in the iQpump drive should be operating normally.

Always turn OFF the input power before beginning inspection. Confirm that the digital operator indicators on the front cover have all

turned OFF, and then wait an additional five minutes before beginning the inspection. Be sure not to touch terminals immediately after

the power has been turned off. Doing so can result in electric shock.

Refer to Warnings and Cautions on page 7

.

Table 7.1 Periodic Inspections With No Power Applied

Apply power to the iQpump drive and conduct the following inspection.

Table 7.2 Periodic Inspections With Power Applied

WARNING

Prior to removing any protective cover or wiring any part of the iQpump drive, remove all power sources, including
main input power and control circuit power. Wait a minimum of 5 minutes after power removal, before removing any
cover. The charge lamp located within the iQpump drive should be off prior to working inside. Even if the charge lamp is
off, one must measure the AC input, output, and DC Bus potential to insure safe levels prior to resuming work. Failure to
adhere to this warning may result in personal injury or death.

Item

Inspection

Corrective Action

External terminals,

mounting bolts,

connectors, etc.

Are all screws and bolts tight?

Tighten loose screws and bolts firmly.

Are connectors tight?

Reconnect the loose connectors.

Cooling fins

Are the fins dirty or dusty?

Clean off any dirt and dust with an air gun using clean and dry air

at a pressure between 55-85 psi.

Control PCB

Terminal PCB

Power PCB

Gate Drive PCBs

Is there any conductive dirt or oil mist on the PCBs?

Clean off any dirt and dust with an air gun using clean and dry air

at a pressure between 55-85 psi. Replace the boards if they

cannot be made clean.

Input Diodes

IPMs

Output Transistors

Is there any conductive dirt or oil mist on the modules or

components?

Clean off any dirt and dust with an air gun using clean and dry air

at a pressure between 55-85 psi.

DC bus capacitors

Are there any irregularities, such as discoloration or odor?

Replace the capacitors or iQpump drive.

Item

Inspection

Corrective Action

Cooling fan(s)

Is there any abnormal noise or vibration, or has the total operating time

exceeded 20,000 hours. Check U1-40 for elapsed cooling fan

operation time.

Replace Cooling Fan