5.2 Pump Basic

128

YASKAWA TM.iQp.01 iQpump Drive User Manual

Example: 3600 RPM Pump Motor

Desired Operation: Minimum Speed is 2100 RPM

Solution: Program P1-06 to 35.0Hz (2100 ÷ 3600 x 60 Hz (E1-04) = 35.0 Hz)

Example: 1800 RPM Pump Motor

Desired Operation: Minimum Speed is 1000 RPM

Solution: Program P1-06 to 35.0Hz (1000 ÷ 1800 x 60 Hz (E1-04) = 33.3 Hz)

P1 Loss of Prime Detection

<0032>

P1-12, P1-14

The Loss of prime function can be used to detect a pump system low suction condition. The iQpump Controller continuously monitors
pump motor current and output frequency while operating auto mode.

Enable Loss of Prime Function

Program P1-14 Prime Loss Level to low suction condition current level.

Guideline: Use 40% of the pump motor full load amp rating (Parameter E2-01)

Operation

If the iQpump Controllers’ output frequency is at maximum (Parameter E1-04) and the pump motor output current level drops below P1-

14 Prime Loss Level for the time programmed in P1-12 Not Maintaining Set Point and Loss of Prime the iQpump drive will fault and

display “LOP”.

Table 5.8

Note: Loss of prime function is only active when the maximum numbers of pumps defined by P1-01 are running at maximum

frequency.

Figure 5.50 Loss of Prime (LOP) Fault

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P1-12



<0032>

0107H

Not Maintaining
Setpoint and Loss of
Prime Time
SetPoint-LOP Tim

Delay time before a Not Maintaining SetPoint or Loss of Prime Time
fault occurs. Pump protection criteria specified in P1-11 or P1-14
must be met for the Drive to fault. The Drive will coast to a stop
when a fault occurs. A value of 0 disables both Loss of Prime and
Not Maintaining SetPoint faults.

0 to 3600

sec

60 sec

Pump Quick

Setup

P1-14



0109H

Prime Loss Level
Prime Loss Level

Used to detect loss of prime in the pump. If output current drops
below this level for the time specified in P1-12 and the output
frequency is at fmax, a “Loss Of Prime” fault occurs. The Drive will
coast to a stop when a fault occurs.

0 to 1000.0

A

0.0 A

Pump Quick

Setup

 Denotes that parameter can be changed when the Drive is running.

-DRIVE-

Loss of Prime

LOP

U2-04 =
U2-05 =

0.00 Hz
0.00 A