4.1 Start Up

68

YASKAWA TM.iQp.01 iQpump Drive User Manual

THIS COMPLETES THE iQpump DRIVE START UP PREPARATION.

… 25. Wire all necessary control wires to the iQpump drive.

… 26. Ensure that the power leads are connected to the R/L1, S/L2 and T/L3 terminals in the iQpump drive.

… 27. Tighten all of the three-phase power and ground connections. Please check that all control and signal terminations are tight.

… 28. Inspect the control circuit connections (including the shield) and determine if a motor “safety circuit” is connected.

If normally closed, these contacts may be wired in series with the RUN command contacts, which are between terminals S1 and

SN of the iQpump drive. No special programming is required. Refer to Chapter 2.

Alternately, these contacts could be wired between terminals S3 and SN as External Fault Inputs, and may be either normally

closed or normally open contacts.

… 29. Record any other connections to the iQpump drive using the blank terminal connection drawing in Chapter 2 – Electrical

Installation (Fig. 2.9) to determine if special programming is required for the following:

Multi-function Inputs – refer to Appendix A.

Multi-function Outputs – refer to Appendix A.

Multi-function Digital Inputs – refer to Appendix A.

Multi-function Analog Outputs – refer to Appendix A.

Serial Communications – refer to Appendix A.