5.3 Pump Protection

130

YASKAWA TM.iQp.01 iQpump Drive User Manual

5.3

Pump Protection

P2 Shutdown Pump System When Running at Low Speed (Sleep)

P2-01, P2-02, P2-03

To protect the pump from operating at very low speeds causing excessive pump wear the iQpump Controller offers a function to

shutdown (Sleep) the pump system.

Select Signal to Monitor

The system level to monitor no-flow operation can be selected with parameter

P2-01 Sleep Level Type

:

Table 5.9

Setup Sleep Level (P2-02)

Sleep Detection level can be setup with

P2-02 Sleep Level

. The Sleep Level units for P2-02 depend on the selection of parameter P2-01

(System Units).

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P2-01

060AH

Sleep Level Type
Sleep Lvl Type

Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
Note:

Feedback depends on PID direction operation.

Displays a “Sleep” Alarm when active.

0 to 2

0

Pump Quick

Setup

P2-02



060BH

Sleep Level
Sleep Level

Sleep activates when selected level (P2-01) reaches programmed
sleep level for time specified in P2-03. The level type is determined
by P2-01. A value of 0 disables this function. This function is only
active during running while operating in auto mode.
Display Units for Sleep Level P2-02 when P2-01 is programmed for
the following:
P2-01 = 0: >Display based on “Hz”
P2-01 = 1: >Display based on “A”
P2-01 = 2: >Display based on P1-02 Selection
Note:

When P2-01 is set for a value of 2, display units will be

dependent on P1-02 setting.

0 to 6000.0

0.0

Pump Quick

Setup

P2-03



060CH

Sleep Delay Time
Sleep Delay Time

Delay time before Drive enters sleep mode when criteria is met as
defined by parameter P2-02.

0 to 3600

sec

10 sec

Pump Quick

Setup