186

YASKAWA

TM.iQp.01 iQpump Drive User Manual

P3-02



0615H

Drive Multi/Maximum
Level
Max-Multi Level

Sets the maximum level used for multiplex pumping operation.
Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.

P3-01=0:

When the output frequency rises above the level

programmed in P3-02 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure (H2-XX = 40, 41).

P3-01=1:

Not Used.

P3-01=2:

When the output frequency rises above level programmed in

P3-02 and the delta feedback (setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure (H2-XX = 40, 41).

0.0 to

120.00

59.0 Hz Programming

149

P3-03



0616H

Add Pump Delta Level
Add Pump D-Lvl

Sets the level used for multiplex pumping operation. The parameter is
active when P3-01 =1 or P3-01 = 2 is selected.

P3-01=0:

Not Used.

P3-01=1:

When the delta feedback (setpoint minus feedback) has

exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure. (H2-XX = 40, 41).

P3-01=2:

When the output frequency rises above level programmed in

P3-02 and the delta feedback (Setpoint minus feedback) has exceeded
the level programmed in P3-03 for a time specified in P3-04, the next
available pump will be added to the system by means of a multi-
function digital output closure. (H2-XX = 40, 41).

Note:

Do not program this level too close to the system setpoint or

excessive cycling of the pump system may occur.

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Programming

150

P3-04



0617H

Add Pump Delay Time
Add Pump Dly Tm

Sets the delay time before a pump is added to the system. Works in
conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.

0 to 3600

2 sec

Programming

150

P3-05



0618H

Shutdown Pump Delta
Level
Shdn Pump D-Lvl

Sets the level used for multiplex pumping operation. Parameter is
active when P3-01 = 1 or P3-01 = 2 is selected.

P3-01=0:

Not Used.

P3-01=1:

When the delta feedback (feedback minus setpoint) has

exceeded the level programmed in P3-05 for a time specified in P3-
06,the last pump that was brought online will be shutdown by means of
a multi-function digital output opening. (H2-XX = 40, 41).

P3-01=2:

When the output frequency drops below level programmed

in P3-09 or P3-10 (depends on last pump running) and the delta
feedback (feedback minus setpoint) has exceeded the level
programmed in P3-05 for a time specified in P3-06, the last pump that
was brought online will be shutdown by means of a multi-function
digital output opening. (H2-XX = 40, 41).

Note:

Do not program this level too close to the system setpoint or

excessive cycling of the pump system may occur.

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Programming

150

P3-06



0619H

Shutdown Pump Delay
Time
Shdn Pump Dly Tm

Sets the delay time before one of the additional across the line pumps is
shutdown.Works in conjunction with parameters P3-02 and P3-03.

0 to 3600

5 sec

Programming

151

P3-07



061AH

Multi Pump Setpoint
Increase
MP Setpoint Inc.

Sets the amount the Drive’s setpoint will decrease for each time a new
pump is brought offline.
Pump 1: Setpoint.
Pump 1+2: Setpoint + P3-07.
Pump 1+2+3: Setpoint + (2 x P3-07).

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Programming

151

P3-08



061BH

Multi Pump Setpoint
Decrease
MP Setpoint Dec.

Sets the amount the Drive’s setpoint will increase for each time a new
pump is brought online.
Pump 1: Setpoint.
Pump 1+2: Setpoint - P3-08.
Pump 1+2+3: Setpoint - (2 x P3-08).

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Programming

152

 Denotes that parameter can be changed when the Drive is running.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.