Third party serial communication converters, Rs232-rs485 / usb - rs485 converters, Ac and dc reactor – Yaskawa iQpump Drive User Manual User Manual

Page 225: Noise filter

Advertising
background image

E.4 Third Party Serial Communication Converters RS232-RS485 / USB - RS485 Converters

YASKAWA

TM.iQp.01 iQpump Drive User Manual

225

AC and DC Reactor

When using models P7U20P4 thru P7U2018 and P7U40P4 thru P7U4018 on a power supply transformer with a capacity of 600kVA or

more, install an AC or DC reactor. The reactor improves the input power factor and provides protection to the rectifier circuit within the

iQpump drive.

Noise filter

Use a noise filter exclusively for the iQpump drive if radio noise generated from the iQpump drive causes other control devices to

malfunction.

E.4

Third Party Serial Communication Converters
RS232-RS485 / USB - RS485 Converters

The iQpump drive has been tested with these Serial/USB to RS/485 converters listed in this document and approved for use with the

PumpScada software. Identical converters can be used but proper communication is not guaranteed.

RS232 Serial Port to RS485 Converters

Manufacturer: Telebyte, Inc

Model: Telebyte T285

Website: www.telebyteusa.com

Table E.5 T285 Module Dipswitch Settings

Note: DB25M to DB9F and serial cable are not included with the converter.

Manufacturer: ATEN
Model: IC485AI

Website: www.aten-usa.com/

TD Control

RTS Control

220 Ohm Term

Two-Wire Mode

Four-wire Mode

Mode

SW1

SW2

SW3

SW4

SW5

RS-485

Two-Wire Transmitter
enabled by TD

ON OFF OFF

ON OFF

Advertising