5.1 iQpump Basic Programming Parameters

96

YASKAWA TM.iQp.01 iQpump Drive User Manual

Figure 5.11 DC Injection Braking to Stop

Important: If an overcurrent (OC) fault occurs during DCInj to Stop, lengthen the Minimum Baseblock Time (L2-03) until the fault no
longer occurs.

3: Coast w/Timer: When the Run command is removed, the iQpump drive will turn off its output and the motor will coast to a stop. If a
Run command is input before time T (operation wait time) expires, the iQpump drive will not run and the Run command will need to be

cycled before operation can occur. The time T (operation wait time) is determined by the output frequency when the Run command is

removed and the active deceleration time (C1-02).

Figure 5.9

Figure 5.12 Coast to Stop with Timer

b2 DC Braking

The DC Braking Group contains parameters associated with the DC injection braking feature. Parameters involving the starting

frequency, current level, braking time, and motor pre heat current level are located here.

b2-01 DC Injection Braking Start Frequency

Setting Range: 0.0 to 10.0 Hz

Factory Default: 0.5 Hz

Parameter b2-01 sets the output frequency where the iQpump drive begins DC Injection during Ramp to stop in order to lock the rotor of
the motor and established the end point of the ramp. If b2-01 < E1-09 (Minimum Frequency), then DC Injection begins at E1-09.

Parameter b2-01 also determines the output frequency that the iQpump drive must be at or below before a Zero Speed condition is

considered true. This affects any digital output configured as a Zero Speed signal (H2-0x = “1: Zero Speed”).

ON

OFF

Run Command

Output Frequency

Drive Output Voltage Interrupted

DC Injection Brake

DC Injection Brake Time

Minimum Baseblock

Time (L2-03)

100 %

0 %

D

C

Injec

tion Br

ak

e T

ime

b2-04 x 10

b2-04

10%

100% (Maximum

Output Frequency)

b2-04

(CLOSED)

(OPEN)

Run Command

Output Frequency

Drive Output

Voltage

Interrupted

OFF

ON

Timer Value T

(C1-02)

100 %

0 %

Operat

io

n W

ai

t T

im

e (T

)

Deceleration

Time (C1-02)

Minimum

Baseblock

Time (L2-03)

Minimum

Output

Frequency

100% (Maximum

Output

Frequency)

Output Frequency at Stop Command Input

Ignored

Run Command

Timer Value T

(OPEN)

(CLOSED)