D.1 Using Modbus Communication

210

YASKAWA

TM.iQp.01 iQpump Drive User Manual

■

Related Parameters

Table D.2 Serial Communication Related Parameters

Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:

1. Monitoring operation status of the iQpump drive.
2. Setting and reading iQpump drive parameters.

3. Resetting faults.

4. Input multi-function commands.
IMPORTANT: An OR operation is performed between the multi-function command input from the DDC and the command input from

multi-function digital input terminals S3 to S7.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

b1-01

0180H

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

0

Pump Quick

Setup

b1-02

0181H

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

0

Pump Quick

Setup

H5-01

0425H

Drive Node Address
Serial Com Adr

Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*
Note:

An address of “0” disables serial com.

0 to 20

(H5-08=0)

0 to FF

(H5-08=1)

0 to 63

(H5-08=2)

1F

Programming

H5-02

0426H

Communication Speed
Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud

0 to 4

3

Programming

H5-03

0427H

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

H5-04

0428H

Stopping Method after
Communication Error
Serial Fault Sel

Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

H5-05

0429H

Communication Error
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.

0 or 1

1

Programming

H5-06

042AH

Drive Transmit Wait
Time
Transmit WaitTIM

Sets the time from when the Drive receives data to when the Drive
sends data.

5 to 65

5 ms

Programming

H5-07

042BH

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

1

Programming

H5-09

0435H

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.

0.0 to 10.0
(H5-08=0)
0.0 to 10.0
(H5-08=1)
0.0 to 90.0
(H5-08=2)

2.0 sec

Programming

 Denotes that parameter can be changed when the iQpump drive is running.
* After these parameters are changed, iQpump drive power must be cycled before the changes will take effect.
# Hex, see

page A-30

.