5.1 iQpump Basic Programming Parameters

112

YASKAWA TM.iQp.01 iQpump Drive User Manual

H3-09 Terminal A2 Function Selection

The A2 analog input can be programmed to perform many different functions. The setting of parameter H3-09 determines which of the

following functions the A2 analog input will perform.

Function: Frequency Bias

Setting: 0

By setting H3-09 = “0: Frequency Bias,” the A2 analog input will serve as a bias signal to the A1 Speed Command. The effect of using
A2 for a frequency bias is that the level of the A2 analog input will be summed with the level of the Speed Command analog input (A1).

For example, if H3-02 = 100%, H3-03 = 0%, and the A2 analog input level is 1 Vdc, the Speed Command profile will look like the figure

below. If A1 = 0 Vdc the Speed Command would be 10% of the programmed maximum frequency because A1 (0 Vdc) + A2 (1 Vdc) = 1
Vdc.

Figure 5.41 Effect of Frequency Bias Function on Speed Command

It should be noted that the bias applied by the A2 analog input functions differently than the level set by the H3-03. If both biases are used
simultaneously they will sum together.

The level of the A1 analog input, as a percentage of the maximum input (either 10 Vdc or 20 mA), can be viewed by the U1-15 monitor.

The level of the A2 analog input, as a percentage of the maximum input, can be viewed by the U1-16 monitor.

The bias applied by setting H3-09 = “0: Frequency Bias,” can be used in conjunction with the parameter bias H3-03. In that case the H3-

03 bias is applied first which changes the slope of the Speed Command vs. Terminal A1 Voltage graph. Then the level of the A2 analog

input is summed with the A1 analog input level, which in effect shifts the Speed Command vs. Terminal A1 Voltage graph upwards or
downwards but does not change the slope of the line.

Figure 5.42 Frequency Bias Applied to Analog Speed Command

Setting

Description

0

Frequency Bias

2

Aux Reference

B

PI Feedback (factory default)

D

Frequency Bias 2

E

Motor Temperature

16

PI Differential

1F

Not Used

0V

10%
Bias

Terminal A1 Voltage

S

pee

d

C

omman

d

10

9V

H3-02

1V

10V

Input

V

A2 Input

Factory Default

S

peed

C

o

mmand

10V

A1 Voltage

S

peed

C

o

mmand

A1 Voltage

10V

H3-03

H3-02

With H3-03 applied

S

peed

A1 Voltage

10V

With both H3-03 and analog input bias

(H3-09=0) applied

H3-02

H3-03

S

peed

Command

Sp

e

e

d

Co

mm

an

d

S

p

eed

C

o

mmand