D.3 Modbus Data Tables

YASKAWA

TM.iQp.01 iQpump Drive User Manual

217

Broadcast Data

The following table shows the broadcast data. Broadcast data can be written to.

Table D.8 Broadcast Data

Enter Command

When writing parameters to the Drive from the PLC using Modbus communication, the parameters are temporarily stored in the constant

data area in the Drive. To enable these parameters in the parameter data area, use the Enter command.

There are two types of Enter commands:

1. 1. Enter commands that enable parameter data in RAM

2. 2. Enter commands that write data to EEPROM (non-volatile memory) in the Drive at the same time as enabling data in RAM.
The following table shows the Enter command data. Enter command data can only be written.

The Enter command is enabled by writing 0 to register number 0900H or 0901H.

Table D.9 Enter Command

IMPORTANT: The maximum number of times you can write to EEPROM using the Drive is 100,000. Do not frequently execute Enter
commands (0900H) written to EEPROM. The Enter command registers are write-only. Consequently, if reading these registers, the

register address will become invalid (Error code: 02H).

Register Address

Contents

0001H

Operation signal

Bit 0

Run command 1: Operating 0: Stopped

Bit 1

Reverse operation command 1: Reverse 0: Forward

Bits 2 and 3

Not used

Bit 4

External error 1: Fault (set using H1-01)

Bit 5

Error Fault 1: Reset command (set using H1-02)

Bits 6 to B

Not used

Bit C

Multi-function digital input terminal S5 input

Bit D

Multi-function digital input terminal S6 input

Bit E

Multi-function digital input terminal S7 input

Bit F

Not used.

0002H

Frequency reference

30000/100%

Note: Bit signals not defined in the broadcast operation signals use local node data signals continuously.

Register No.

Contents

0900H

Write parameter data to EEPROM

0910H

Parameter data is not written to EEPROM, but refreshed in RAM only.