4.7 High Feedback Level Alarm and Fault Setup

YASKAWA TM.iQp.01 iQpump Drive User Manual

81

4.7

High Feedback Level Alarm and Fault Setup

P1-09, P1-10, P1-13

Table 4.14

The iQpump drive continuously monitors the systems feedback device and has the ability to show an alarm and/or fault the iQpump drive
when the feedback signals rise above a programmed high feedback level (P1-09) for a programmed high feedback level fault delay time

(P1-10).

The hysteresis level (P1-13) determines the high feedback alarm turn-off level. In case of a high feedback alarm, the alarm message will
turn-off when the feedback level falls below the programmed high feedback level (P1-09) minus the hysteresis level (P1-13).

Figure 4.6 High Feedback Alarm and Fault Displays

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P1-09



0608H

High Feedback Level
High FB Level

The Drive will display a “High Feedback Level (HFB)” alarm when
the feedback level rises above the programmed level. The alarm will
turn off when the feedback level falls below the programmed High
Feedback Level minus the Hysteresis Level (P1-13). This function is
active during running in the hand mode, auto mode, pre-charge and
thrust-bearing mode.

0.0 to

6000.0

(system

units

P1-02)

155.0

(system

units

P1-02)

Pump Quick

Setup

P1-10



0609H

High Feedback Level
Fault Delay Time
Hgh Lvl FLT Time

The Drive will initiate a “High Feedback Fault (HFB)” when the
feedback level rises above the programmed level for a time specified
in P1-10. The Drive will coast to a stop when a fault occurs. This
function is active during running in all operation modes.

0 to 3600

2 sec

Pump Quick

Setup

P1-13



0108H

Hysteresis Level
Hysteresis Level

Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.

0.0 to
100.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Pump Quick

Setup

 Denotes that parameter can be changed when the Drive is running.

High Feedback Alarm

High Feedback Fault

-DRIVE-

High Feedback

High FBK Sensed

Rdy

-DRIVE-

High Feedback

HFB

U2-04 =
U2-05 =

0.00 Hz
0.00 A