4.6 Low Feedback Level Alarm and Fault Setup

YASKAWA TM.iQp.01 iQpump Drive User Manual

79

4.6

Low Feedback Level Alarm and Fault Setup

P1-07, P1-08, P1-13

Table 4.13

The iQpump drive continuously monitors the systems feedback device and has the ability to show an alarm or even fault the iQpump
drive when the feedback signals fall below a programmed low feedback level (P1-07) for a programmed low feedback level fault delay

time (P1-08).

The hysteresis level (P1-13) determines the low feedback alarm turn-off level. In case of a low feedback alarm, the alarm message will
turn-off when the feedback level rises above the programmed low feedback level (P1-07) plus the hysteresis level (P1-13).

Figure 4.1

Figure 4.4 Low Feedback Alarm and Fault Displays

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P1-07



0606H

Low Feedback Level
Low FB Level

The Drive will display a “Low Feedback (LFB)” alarm when the
feedback level falls below the programmed level. The alarm will turn
off when the feedback level rises above the programmed Low
Feedback Level plus the Hysteresis Level (P1-13). A value of 0
disables this function. This function is only active during running
while operating in the auto mode.

0.0 to

6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Pump Quick

Setup

P1-08



0607H

Low Feedback Level
Fault Delay Time
Low Lvl FLT Time

The Drive will display a “Low Feedback/Water (LFB/LW)” alarm
when the feedback level falls below the programmed level for a time
specified in P1-08. The Drive will coast to a stop when a fault occurs.
A value of 0 disables this function. This function is only active
during running while operating in the auto mode.

0 to 3600

sec

5 sec

Pump Quick

Setup

P1-13



0108H

Hysteresis Level
Hysteresis Level

Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.

0.0 to
100.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Pump Quick

Setup

 Denotes that parameter can be changed when the Drive is running.

Low Feedback Alarm

Low Feedback Fault

-DRIVE-

Low Feedback

Low FBK Sensed

Rdy

-DRIVE-

Low FB / Water

LFB/LW

U2-04 =
U2-05 =

0.00 Hz
0.00 A