5.1 iQpump Basic Programming Parameters

YASKAWA TM.iQp.01 iQpump Drive User Manual

91

Figure 5.3

Figure 5.4 External Analog Signal Setpoint Reference

If you want the iQpump drive to receive the “Auto Setpoint” from serial communication: Set b1-01 = “2: Serial Com,” and connect
the RS-485/422 serial communications cable to terminals R+, R-, S+, and S- on the control I/O terminal block.

Refer to

Figure 5.5

for the connection diagram using a PC to provide the auto setpoint reference to the iQpump drive. Further information

regarding Modbus address and communication protocols are referenced in the

Section Appendix: A

and

Section Appendix: D

.

Figure 5.4

Figure 5.5 Connection Diagram of PC or PLC

If you want the iQpump drive to receive the “Auto Setpoint” for a network communication option card: Set b1-01= “3: Option
PCB”, and plug a network option board (p/n SI-J) into the 2CN port on the iQpump drive Control PCB. Consult the manual supplied with

the option board for instructions on integrating the iQpump drive into the network system.

The iQpump drive can support the following network communication options. Refer to the appropriate Installation Guide (IG) and

Technical Manual (TM) for further details. These network communications documents can be located at

http://iQpump.yaskawa.com

.

• Profibus DP Option Card CM061

Manual: IG.AFD.12

• DeviceNet Option Card CM05X

Manual: IG.AFD.14

• Modbus Plus Option Card CM071

Manual: IG.AFD.17

• Modbus TCP/IP Option Card CM090

Manual: IG.AFD.25

• EtherNet/IP Option Card CM092

Manual: IG.AFD.26