5.1 iQpump Basic Programming Parameters

YASKAWA TM.iQp.01 iQpump Drive User Manual

125

o3-02 Read Allowed Selection

The digital operator has parameter COPY capabilities via built in non-volatile memory. The digital operator can READ all of the

parameters in the iQpump drive and store them for later WRITE back to the iQpump drive or into an iQpump drive with the same product
code and software number. In order to read the parameter values and store them in the digital operator, select o3-02 = “1: Enabled”. If you

attempt to READ the data, which overwrites any previously stored data, without first setting o3-02 = “1: Enabled,” you will get the

following error:

After setting o3-02 = “1: Enabled,” it is possible to store parameter values in the digital operator by setting o3-01 = 1 (INV

→OP READ).

A successful READ of the parameter values will display:

An error may occur while saving the parameter values to the digital operator’s memory. If an error is displayed, press any key to cancel
the error display and return to parameter o3-01. Error displays and their meanings are covered in Chapter 6: Diagnostics and

Troubleshooting of the P7 Users Manual (TM.iQp.01). To COPY parameter values into a Drive, set o3-01 = “2: OPÆ INV WRITE”.

During the writing of the parameter values into the iQpump drive the digital operator will display:

A successful COPY of the parameter values will display:

An error may occur while writing the parameter values to the Drive. If an error is displayed, press any key to cancel the error display and

return to parameter o3-01. Error displays and their meanings are covered in Chapter 6: Diagnostics and Troubleshooting of the iQpump
User Manual (TM.iQp.01).

It is possible to compare the parameter values stored in the digital operator with the parameter values currently in the iQpump drive by

using the VERIFY function. This VERIFY function should not be confused with the “-VERIFY-” that is displayed on the digital operator
when viewing the “Modified Constants” menu. To VERIFY the parameter values in the iQpump drive as compared with those stored in

the digital operator, set o3-01 = “3: OP´INV VERIFY”. During the comparing of the parameter values into the iQpump drive the digital

operator will display:

Setting

Description

0

Disabled (factory default)

1

Enabled

-ADV-

PRE

READ IMPOSSIBLE

-ADV-

READ

READ COMPLETE

-ADV-

COPY

OP

→INV COPYING

-ADV-

COPY

COPY COMPLETE