TM.iQp.01 iQpump Drive User Manual

183

o3-02

0516H

Read Allowed Selection
Read Allowable

Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are allowed.
1: Enabled - Copying allowed

0 to 1

0

Programming

120

Pump Basic

P1-01

0600H

Pump Mode
Pump Mode

Select type of control operation.
0: Drive Only (Simplex)
1: Drive + 1 Pump
2: Drive + 2 Pumps

0 to 2

0

Programming

122

P1-02

0601H

System Units
System Units

0: WC:InchOfWater
1: PSI:lb/SqrInch
2: GPM:Gallons/Min
3: F:DegFarenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic m/Hr
6: LPH:Liters/Hr
7: LPS:Liters/sec
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Ft: Feet

<0032>

12:%: Percent

0 to 12

1

Pump Quick

Setup

124

P1-03

0602H

Feedback Device Scaling
Fb Dev Scaling

Scaling of feedback device in user units (P1-02=1, e.g. 150PSI).
Digits 1 through 4 set the maximum feedback number. Digit 5
determines the number of decimal places.
Digit 5 = 0: Number format is XXXX
Digit 5 = 1: Number format is XXX.X
Digit 5 = 2: Number format is XX.XX
Digit 5 = 3: Number format is X.XXX
Examples:
01000 = 1000
13000 = 300.0
25000 = 50.00
32000 = 2.000

1 to 36000

(system

units P1-

02)

00145

Pump Quick

Setup

124

P1-04



0603H

Start Level
Start Level

Drive starts when the feedback level drops below the start level for a
time specified in P1-05. This level also specifies the wake up level
when the drive is in Sleep Mode.
Note:

When PID operates in the reverse mode, the feedback value has

to rise above the start level for the time programmed in P1-05 for the
system to start. A value of 0 disables this function.

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Pump Quick

Setup

125

P1-05



0604H

Start Level Delay Time
S-Lvl Delay Time

Drive starts when the feedback level drops below the start level for a
time specified in P1-05.

0 to 3600

0 sec

Pump Quick

Setup

125

P1-06



0605H

Minimum Pump
Frequency
Min. Pump Freq.

Minimum drive frequency when operated in the auto mode.
Programmed value will limit minimum PID output. Minimum value
has to be programmed to a value smaller than P3-09 and P3-10 when
Drive is operating in the multiplex mode (P1-01).

0.0 to

120.0 Hz

35.0 Hz

Pump Quick

Setup

125

P1-07



0606H

Low Feedback Level
Low FB Level

The Drive will display a “Low Feedback (LFB)” alarm when the
feedback level falls below the programmed level. The alarm will turn
off when the feedback level rises above the programmed Low
Feedback Level plus the Hysteresis Level (P1-13). A value of 0
disables this function. This function is only active during running while
operating in the auto mode.

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Pump Quick

Setup

125

P1-08



0607H

Low Feedback Level
Fault Delay Time
Low Lvl FLT Tim

e

The Drive will display a “Low Feedback/Water (LFB/LW)” alarm
when the feedback level falls below the programmed level for a time
specified in P1-08. The Drive will coast to a stop when a fault occurs.
A value of 0 disables this function. This function is only active during
running while operating in the auto mode.

0 to 3600

sec

5 sec

Pump Quick

Setup

125

P1-09



0608H

High Feedback Level
High FB Level

The Drive will display a “High Feedback Level (HFB)” alarm when
the feedback level rises above the programmed level. The alarm will
turn off when the feedback level falls below the programmed High
Feedback Level minus the Hysteresis Level (P1-13). This function is
active during running in the hand mode, auto mode, pre-charge and
thrust-bearing mode.

0.0 to

6000.0

(system

units P1-

02)

155.0

(system

units P1-

02)

Pump Quick

Setup

126

P1-10



0609H

High Feedback Level
Fault Delay Time
Hgh Lvl FLT Time

The Drive will initiate a “High Feedback Fault (HFB)” when the
feedback level rises above the programmed level for a time specified in
P1-10. The Drive will coast to a stop when a fault occurs. This function
is active during running in all operation modes.

0 to 3600

2 sec

Pump Quick

Setup

126

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.