6.3 Alarm Detection

YASKAWA TM.iQp.01 iQpump Drive User Manual

145

Pump Alarm Messages Generated

Digital Operator

Display

Description

Cause

Corrective Action

Low Feedback

Low FB Sensed

Low Feedback Level Alarm

Feedback signal is too low.

The feedback level has dropped below the low
feedback level (P1-07). Low feedback fault is
active in Auto Mode when the iQpump drive is

running.

Feedback level greater than the low
feedback level (P1-07).

High Feedback

High FB Sensed

High Feedback Alarm

Feedback signal is too high.

The feedback level has risen above P1-09 level.
High feedback alarm is active in Hand Mode, Auto

Mode, Pre-charge and Thrust Mode when the
iQpump drive is running.

Feedback level lower than the high

feedback level (P1-09).

Start Delay

Timer Active

Start Delay

Start delay timer is active.

Displays when the iQpump drive is about to start.

The feedback level is fallen below the start level
(P1-04) and the start delay timer is active. Once the
start level delay time (P1-05) expires, the iQpump
drive will start.

When PI output level selection (b5-09) is

programmed for reverse, the alarm is displayed
when the feedback level falls rises above start level
(P1-04).

Wait for the start level delay time to

expire.

Program a different start level delay
time.

Sleep Active

Wait for Start

During Sleep / Wait for Start

Sleep mode waiting for
appropriate levels to start.

Displays when the iQpump drive is in the “sleep”
mode or when the iQpump drive is waiting for
feedback level to drop below start level (P1-04).

When PI output level selection (b5-09) is

programmed for reverse, the alarm is displayed
when feedback level falls below start level (P1-04).

Wait for the sleep mode time to
deactivate.

Program a different start level or

disable sleep mode.

Pre-Chg Mode

Pre-Chg Active

During Pre-Charge

The pre-charge mode is
active.

Displays when “Pre-charge” mode is active.

Wait for pre-charge mode to
deactivate.

Disable pre-charge mode.

Pump Cycling

Pump Over Cycle

Pump Over Cycle

The number of cycles is
exceeded.

VFD Controlled Pump exceeds number of Normal
Operation to Sleep Mode Cycles. Cycle limit (P2-

09) for time specified in P2-10.

Adjust sleep parameters group P2 to
prevent system from cycling.

Thrust Mode

Thrust Active

Thrust Bearing

The thrust bearing mode is
active.

Displays when “Thrust Bearing” mode is active.

Wait for thrust bearing mode to
deactivate.

Disable thrust bearing mode.