background image

4.5 Use Feedback Level to Start iQpump Controller

YASKAWA TM.iQp.01 iQpump Drive User Manual

77

4.5

Use Feedback Level to Start iQpump Controller

P1-04, P1-05

Table 4.12

The iQpump drive has a built-in function that allows the system to start regulating when the feedback signal drops below a programmed
start level (P1-04) for a programmed start level delay time (P1-05).

In many constant pressure applications, it is necessary to start the pump at different feedback levels along with a timer to ensure that the

pump does not cycle on and off, if the pressure is floating too close to the start level. Due to system losses and leaks in pipes, the pressure
will slowly decrease and it is desirable for the iQpump drive system to sense this changing level and automatically restart the automatic

regulation back to desired setpoint.

Example: Constant Pressure System
System Units set to PSI (P1-02 = PSI)

System Setpoint set for 80 PSI

Pressure Transducer: 150 PSI

Desired Operation:

Pump System should start regulating when pressure drops below 70 PSI.

Solution:
Program P1-04 to 70 PSI and P1-05 to 2 sec.

Figure 4.2 Constant Pressure System

Note: In order for the system to start regulating, the Run command has to be present. (See 4.3 Pump System Start/Stop).

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

P1-04



0603H

Start Level
Start Level

Drive starts when the feedback level drops below the start level for a
time specified in P1-05. This level also specifies the wake up level
when the drive is in Sleep Mode.
Note: When PID operates in the reverse mode, the feedback value
has to rise above the start level for the time programmed in P1-05 for
the system to start. A value of 0 disables this function.

0.0 to

6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Pump Quick

Setup

P1-05



0604H

Start Level Delay
Time
S-Lvl Delay Time

Drive starts when the feedback level drops below the start level for a
time specified in P1-05.

0 to 3600

0 sec

Pump Quick

Setup

 Denotes that parameter can be changed when the Drive is running.

Display shows Sleep Active message when iQpump waits for feedback signal to fall below
programmed level P1-04.

Display shows Start Delay message when feedback signal has dropped below programmed level P1-04

and the system is about to start after P1-05 timer expires.

-DRIVE-

Sleep Active

Wait for Start

Rdy

-DRIVE-

Start Delay

Timer Active

Rdy