H4-04

0420H

Terminal AM Monitor
Selection
Terminal AM Sel

Selects which monitor will be output on terminals AM and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = Drive rated current)
6: Output Voltage (100% = 230 V or 100% = 460 V)
7: DC Bus Voltage (100% = 400 V or 100% = 800 V)
8: Output kWatts (100% = Drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint

Note:

100% = 10 V DC output * AM gain setting (H4-05).

1 to 38

<0032>

8

Programming

79

H4-05



0421H

Terminal AM Gain
Setting
Terminal AM Gain

Sets terminal AM output voltage (in percent of 10 V) when selected
monitor is at 100% output.

0.0 to

1000.0

50.0%

Programming

79

H4-06



0422H

Terminal AM Bias
Setting
Terminal AM Bias

Sets terminal AM output voltage (in percent of 10 V) when selected
monitor is at 0% output.

–110.0 to

110.0

0.0%

Programming

79

H4-07

0423H

Terminal FM Signal
Level Selection
AO Level Select1

0: 0 - 10 Vdc
2: 4-20 mA*

0 or 2

0

Programming

80

H4-08

0424H

Terminal AM Signal
Level Selection
AO Level Select2

0: 0 - 10 Vdc
2: 4-20 mA*
* An analog output of 4 - 20 mA cannot be used with the standard
terminal board. Therefore an optional terminal board (with shunt
connector CN15) is needed.

0 or 2

0

Programming

80

 Denotes that parameter can be changed when the drive is running.

Serial Com Setup

H5-01

0425H

Drive Node Address
Serial Com Adr

Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*

Note:

An address of “0” disables serial com.

0 to 20

(H5-08=0)

0 to FF

(H5-08=1)

0 to 63

(H5-08=2)

1F

Programming

93

H5-02

0426H

Communication Speed
Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud

0 to 4

3

Programming

93

H5-03

0427H

Communication Parity
Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

93

H5-04

0428H

Stopping Method after
Communication Error
Serial Fault Sel

Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

94

H5-05

0429H

Communication Error
Detection Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.

0 or 1

1

Programming

94

H5-06

042AH

Drive Transmit Wait
Time
Transmit WaitTIM

Sets the time from when the Drive receives data to when the Drive
sends data.

5 to 65

5 ms

Programming

94

H5-07

042BH

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

1

Programming

94