Monitor list – Yaskawa iQpump Drive User Manual User Manual

Page 190

Advertising
background image

190

YASKAWA

TM.iQp.01 iQpump Drive User Manual

Monitor List

Table 2 Monitor List

Parameter No.

Modbus

Address

Parameter Name Digital

Operator Display

Description

Monitor

U1-01

0040H

Auto Setpoint Reference
Auto: Setpoint

Auto Setpoint Reference (speed command) monitor when in auto mode, frequency reference
(speed command) setting location when in hand mode. Units changeable via P1-02.

U1-02

0041H

Output Frequency
Output Freq

Output frequency monitor in Hz.

U1-03

0042H

Output Current
Output Current

Output current monitor.

U1-06

0045H

Output Voltage
Output Voltage

Displays Drive output voltage.

U1-07

0046H

DC Bus Voltage
DC Bus Voltage

Displays DC bus voltage.

U1-08

0047H

Output Power
Output kWatts

Displays Drive output power.

U1-10

0049H

Input Terminal Status
Input Term Sts

Displays Drive input terminal status.

U1-11

004AH

Output Terminal Status
Output Term Sts

Output terminal ON/OFF check.

U1-12

004BH

Drive Operation Status
Int Ctl Sts 1

U1-13

004CH

Cumulative Operation Time
Elapsed Time

Displays total operating or power-on time of the Drive.

U1-14

004DH

Software Number
FLASH ID

Displays Drive's software number.

U1-15

004EH

Terminal A1 Input Voltage
Term A1 Leve

l

Displays the input voltage on Terminal A1, as a percentage of 10 Vdc.

0

1: FWD. run
(Terminal S1) is ON.
1: REV. run
(Terminal S2) is ON.
1: Multi-function input 1
(Terminal S3) is ON.
1: Multi-function input 2
(Terminal S4) is ON.
1: Multi-function input 3
(Terminal S5) is ON.
1: Multi-function input 4
(Terminal S6) is ON.
1: Multi-function input 5
(Terminal S7) is ON.

0 0 0 0 0 0 0

1: Multi-function Contact 1
output 1 (Terminal M1-M2) is
ON.
1:Multi-function Contact 2
output 1 (Terminal M3-M4) is
ON.
Not used

Not used
1:Fault output
(Terminal MA/MB-MC) is
ON.

0 0 0 0 0 0 0 0

1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Drive operation ready
1: During fault detection
(Minor fault)
1: During fault detection
(Major fault)

0 0 0 0 0 0 0 0

Advertising