Vector control

4.9 Vdc control

Drive Functions

136

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Description of Vdc_max control

,

TVHWS

 WRUTXHJHQHUDWLQJFXUUHQWVHWSRLQW

,

TVHWS

6ZLWFKRQOHYHO

Q

VHWS

Q

DFW

9

GF

FWUODFWLYH

$

_Q_

9

GF

W





W

>9@

W

Figure 4-15 Switching Vdc_max control on/off

The switch-in level for Vdc_max control (r1242) is calculated as follows:
● When the function for automatically detecting the switch-on level is switched off

(p1254 = 0)

r1242 = 1.15 * p0210 (device connection voltage, DC link).

● When the function for automatically detecting the switch-on level is switched on

(p1254 = 1)

r1242 = Vdc_max - 50 V (Vdc_max: overvoltage threshold of the Motor Module)

Function diagrams (see SINAMICS S List Manual)

● 6220 Vdc_max controller and Vdc_min controller

Overview of key parameters (see SINAMICS S List Manual)

● p1240[0...n] Vdc controller or Vdc monitoring configuration
● r1242 Vdc_max controller switch-in level
● p1243[0...n] Vdc_max controller dynamic factor (control)
● p1245[0...n] Vdc_min controller switch-in level (kinetic buffering) (control)
● r1246 Vdc_min controller switch-in level (kinetic buffering) (control)
● p1247[0...n] Vdc_min controller dynamic factor (kinetic buffering) (control)
● p1250[0...n] Vdc controller proportional gain (control)
● p1251[0...n] Vdc controller integral time (control)
● p1252[0...n] Vdc controller derivative-action time (control)
● p1254 Vdc_max controller automatic detection ON level (control)