Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

368

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Bit

Meaning

Comments

BICO

1

Power-on disable

A restart is only possible by means of OFF1 and

then ON.

6

Power-on disable

0

No power-up inhibit

Power-up is possible.

BO: r0899.6

1

Alarm present

The drive is operational again. No

acknowledgement necessary.
The active alarms are stored in the alarm buffer.

7

Alarm present

0

No alarm present

No active alarm in the alarm buffer.

BO: r2139.7

1

Setpoint-actual value monitoring within tolerance

band
Actual value within a tolerance bandwidth;
The tolerance bandwidth can be parameterized.

8

Following error within the tolerance

range

0

Setpoint/actual value monitoring not within

tolerance band

BO: r2684.8

1

Control required

The PLC is requested to assume control. Condition

for applications with isochronous mode: drive

synchronized with PLC system.

9

Control requested

0

Local operation

Control only possible on device

BO: r0899.9

1

Target position reached

10 Target position reached

0

Target position not reached

BO: r2684.10

1

Reference point set

11 Reference point set

0

Reference point not set

BO: r2684.11

0/1

Acknowledgement, traversing block

12 Acknowledgement, traversing

block activated

0

No effect

BO: r2684.12

1

Drive at standstill

13 Drive at standstill

0

Drive not at standstill

BO: r2199.0

14 Reserved

15 Reserved

STW2 (status word 2)

See function diagram [2454]

Table 10-13 Description of STW2 (status word 2)

Bit

Meaning

Comments

BICO

0

DDS eff., bit 0

BO: r0051.0

1

DDS eff., bit 1

BO: r0051.1

2

DDS eff., bit 2

BO: r0051.2

3

DDS eff., bit 3

Drive data set effective (5-bit counter)

BO: r0051.3