Communication PROFIBUS DP/PROFINET IO

10.2 Communication via PROFIBUS DP

Drive Functions

436

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

For diagnostic purposes, there are the diagnostic parameters r2075 ("PROFIBUS

diagnostics, receive telegram offset PZD") and r2076 ("PROFIBUS diagnostics, transmit

telegram offset PZD"). The parameter r2074 ("PROFIBUS diagnostics, receive bus address

PZD") displays the DP address of the setpoint source of the respective PZD.
r2074 and r2075 enable the source of a slave-to-slave communication relationship to be

verified in the Subscriber.

Note
The Subscribers do not monitor the existence of an isochronous Publisher sign of life.

Alarms and error messages with PROFIBUS slave-to-slave communication

An alarm A1945 signals that a publisher of a device (CU320) is missing or has failed. Any

interruption to the Publisher is also reported by an error F1946 at the affected DO. A failure

of the Publisher will therefore only affect the respective DOs.

A1945

PROFIBUS: Connection of device to Publisher x interrupted

Reaction:

NONE

Acknowledgment:

NONE

Cause:

The cyclic data transfer between this PROFIBUS device and a slave-to-slave

communication publisher was not established or was interrupted.
Examples:
Bus connection interrupted
Publisher failed
New startup of DP master

Remedy:

Check Publisher and bus connections to Publisher, to DP master and between DP master

and Publisher.

F1946 (A)

PROFIBUS: Connection of drive object to Publisher x interrupted

Reaction:

OFF1 (NONE; OFF2; OFF3)

Acknowledgment:

IMMEDIATELY

Cause:

The cyclic data transfer between this drive object and a slave-to-slave communication

Publisher was not established or was interrupted.
Examples:
Bus connection interrupted
Publisher failed
New startup of DP master

Remedy:

Check Publisher and bus connections to Publisher, to DP master and between DP master

and Publisher.