Safety Integrated basic functions

9.7 Commissioning the "STO", "SBC" and "SS1" functions

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

321

No.

Parameter

Description/comments

5


p9652 > 0
p9852 > 0

Enable "Safe Stop 1" function.
Enable "SS1" on the Control Unit
Enable "SS1" on the Motor Module
•

The parameters are not changed until safety commissioning mode has been exited

(i.e. when p0010 ≠ 95 is set).

•

Both parameters are included in the crosswise data comparison and must, therefore,

be identical.

•

The "Safe Stop 1" function is not activated until at least one safety monitoring function

has been enabled (i.e. p9601 = p9801 ≠ 0).

6


p9620 = "Value"
Terminal "EP"

Set terminals for "Safe torque off (STO)".
Set the signal source for STO on the Control Unit.
Wire terminal "EP" (enable pulses) on the Motor Module.
•

Control Unit monitoring channel:
By appropriately interconnecting BI: p9620 for the individual drives, the following is

possible:
– Selecting/deselecting the STO
– Grouping the terminals for STO

•

Motor Module monitoring channel:
By wiring the "EP" terminal accordingly on the individual Motor Modules, the following

is possible:
– Selecting/deselecting the STO
– Grouping the terminals for STO

Note:
The STO terminals must be grouped identically in both monitoring channels.

7


p9650 = "Value"
p9850 = "Value"

Set F-DI changeover tolerance time.
F-DI changeover tolerance time on Control Unit
F-DI changeover tolerance time on Motor Module
•

The parameters are not changed until safety commissioning mode has been exited

(i.e. when p0010 ≠ 95 is set).

•

Due to the different runtimes in the two monitoring channels, an F-DI changeover

(e.g., selection/deselection of STO) does not take immediate effect. After an F-DI

changeover, dynamic data is not subject to a data cross-check during this tolerance

time.

•

Both parameters are included in the crosswise data comparison and must, therefore,

be identical. A difference of one safety monitoring clock cycle is tolerated for the

values.