Basic information about the drive system

12.7 Examples of replacing components

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

501

Action

Reaction

Comments

•

Set p9905 to "1"

•

Alarm disappears

•

The serial number is copied

to the target topology

The serial number is stored in

the RAM of the Control Unit and

has to be copied to the non-

volatile memory with p0971 or

p0977.

The component has been successfully replaced

Example: Replacing a Motor Module/Power Module with a different power rating

Precondition:

The replaced power unit has a different power rating
Vector: Power rating of the Motor Module/Power Module not greater than 4 * motor current

Table 12-13 Example: Replacing a power unit with a different power rating

Action

Reaction

Comments

•

Switch off the power supply

•

Replace the defective

component and connect the

new one

•

Switch on the power supply





Alarm A01420

•

Drive Object CU:
– p0009 = 1
– p9906 = 2
– p0009 = 0
– p0977 = 1


•

Device configuration

•

Component comparison

•

Completing the configuration

•

Data Backup

For p9906=2: Caution
Topology monitoring for all

(!) components heavily

reduced so that DRIVE-CLiQ

lines may be hidden by

mistake.

•

Drive Object component:
– p0201 = r0200
– p0010 = 0
– p0971 = 1


•

Use the code number

•

Completing commissioning

•

Data Backup

The new order number is

stored in the RAM of the

Control Unit and has to be

copied to the non-volatile

memory with p0971 or

p0977.

The component has been successfully replaced