Efficient Networks Siemens Sinamics S120 User Manual

Page 383

Advertising
background image

Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

383

Error code in Gn_XIST2

Table 10-20 Error code in Gn_XIST2

n_XIST2

Meaning

Possible causes / description

1

Encoder error

One or more existing encoder faults.

Detailed information in accordance with drive messages.

2

Zero marker monitoring

3

Abort parking sensor

Parking drive object already selected.

4

Abort find reference

marker

A fault exists (Gn_ZSW.15 = 1)

Encoder has no zero marker (reference marker)

Reference marker 2, 3 or 4 is requested

Switchover to "Measurement on-the-fly" during search for reference marker

Command "Read value x" set during search for reference marker

Inconsistent position measured value with distance-coded reference markers.

5

Abort, retrieve reference

value

More than four values requested

No value requested

Requested value not available

6

Abort flying measurement • No probe configured p0488, p0489

Switch over to "reference mark search" during flying measurement

Command "Read value x" set during flying measurement

7

Abort get measured value • More than one value requested

No value requested.

Requested value not available

Parking encoder active

Parking drive object active

8

Abort absolute value

transmission on

Absolute encoder not available

Alarm bit absolute value protocol set

3841

Function not supported

Encoder 2 status word (G2_STW)

● See G1_STW (table 4-20)

Encoder 2 actual position value 1 (G2_XACT1)

● See G1_XIST1

Encoder 2 actual position value 2 (G2_XACT2)

● See G1_XIST2

Encoder 3 status word (G3_STW)

● See G1_STW (table 4-20)

Advertising