Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

356

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Bit

Meaning

Comments

BICO

Note:

The ramp-function generator cannot be frozen via p1141 in jog mode (r0046.31 = 1).

1

Enable setpoint

6

Enable speed setpoint

0

Inhibit setpoint

Set ramp-function generator input to zero

BI: p1142

0/1

Acknowledge fault

Acknowledge fault

0

No effect

BI: p2103

7

Note:

Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.

8

reserved

-

-

-

9

reserved

-

-

-

1

Master ctrl by PLC
This signal must be set so that the process data

transferred via PROFIdrive is accepted and

becomes effective.

Master ctrl by PLC

0

PLC has no master control
Process data transferred via PROFIdrive is

rejected - i.e. it is assumed to be zero.

BI: p0854

10

Note:

This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via STW1.9 = "1"..

1

Direction reversal

11 Direction reversal

0

No direction reversal

BI: p1113

12 Reserved

1

Motorized potentiometer, setpoint, raise

13 Motorized potentiometer, setpoint, raise

0

Motorized potentiometer setpoint raise not

selected

BI: p1035

1

Motorized potentiometer, lower setpoint

Motorized potentiometer, lower setpoint

0

Motorized potentiometer setpoint lower not

selected

BI: p1036

14

Note:

If motorized potentiometer setpoint raise and lower are 0 or 1 simultaneously, the current setpoint is frozen.

15 reserved

-

-

-

STW1 (control word 1), positioning mode, p0108.4 = 1

See function diagram [2475]

Table 10-5 Description of STW1 (control word 1), positioning mode

Bit

Meaning

Comments

BICO

0/1

ON

Pulse enable possible

0

ON/OFF1

0

OFF1

Braking with the ramp-function generator, then

pulse cancellation and power-on inhibit.

BI: p0840