Basic information about the drive system

12.7 Examples of replacing components

Drive Functions

500

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Action

Reaction

Comments

Load the project from the

Control Unit to the

STARTER (PG)

Configure the replacement

drive and select the current

component

Load the project to the

Control Unit (target system)

Alarm disappears

The new order number is stored

in the RAM of the Control Unit

and has to be copied to the non-

volatile memory with p0971 or

p0977.

The component has been successfully replaced

Example: (p9909 = 1) Replacing a defective component with an identical order number

Precondition:

● The replaced component has an identical order number
● The serial number of the new replacement component must not be contained in the

stored target topology of the Control Unit.

● Topology comparison component replacement active p9909 = 1.

Sequence:

During startup of the Control Unit, the serial number of the new component is automatically

transferred to the target topology and saved.

Example: (p9909 = 0) Replacing a defective component with an identical order number

Precondition:

● The replaced component has an identical order number
● Topology comparison component replacement inactive p9909 = 0.

Table 12-12 Example: Replacing a Motor Module

Action

Reaction

Comments

Switch off the power supply

Replace the defective

component and connect the

new one

Switch on the power supply





Alarm A01425