Basic information about the drive system

12.7 Examples of replacing components

Drive Functions

500

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Action

Reaction

Comments

•

Load the project from the

Control Unit to the

STARTER (PG)

•

Configure the replacement

drive and select the current

component

•

Load the project to the

Control Unit (target system)

•

Alarm disappears

The new order number is stored

in the RAM of the Control Unit

and has to be copied to the non-

volatile memory with p0971 or

p0977.

The component has been successfully replaced

Example: (p9909 = 1) Replacing a defective component with an identical order number

Precondition:

● The replaced component has an identical order number
● The serial number of the new replacement component must not be contained in the

stored target topology of the Control Unit.

● Topology comparison component replacement active p9909 = 1.

Sequence:

During startup of the Control Unit, the serial number of the new component is automatically

transferred to the target topology and saved.

Example: (p9909 = 0) Replacing a defective component with an identical order number

Precondition:

● The replaced component has an identical order number
● Topology comparison component replacement inactive p9909 = 0.

Table 12-12 Example: Replacing a Motor Module

Action

Reaction

Comments

•

Switch off the power supply

•

Replace the defective

component and connect the

new one

•

Switch on the power supply





Alarm A01425