Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions

398

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Error

value

Meaning

Comment

Additional

info

0x78

Parameter %s [%s]: Write access

only in the commissioning state, drive

configuration (device: p0009 = 3).

–

–

0x79

Parameter %s [%s]: Write access

only in the commissioning state,

define drive type (device: p0009 = 2).

–

–

0x7A

Parameter %s [%s]: Write access

only in the commissioning state, data

set basis configuration

(device: p0009 = 4).

–

–

0x7B

Parameter %s [%s]: Write access

only in the commissioning state,

device configuration

(device: p0009 = 1).

–

–

0x7C

Parameter %s [%s]: Write access

only in the commissioning state,

device download

(device: p0009 = 29).

–

–

0x7D

Parameter %s [%s]: Write access

only in the commissioning state,

device parameter reset

(device: p0009 = 30).

–

–

0x7E

Parameter %s [%s]: Write access

only in the commissioning state,

device ready (device: p0009 = 0).

–

–

0x7F

Parameter %s [%s]: Write access

only in the commissioning state,

device (device: p0009 not 0).

–

–

0x81

Parameter %s [%s] may not be

written in download.

–

–

0x82

Transfer of the control authority

(master) is inhibited by BI: p0806.

–

–

0x83

Parameter %s [%s]: requested BICO

interconnection not possible

BICO output does not supply float values. The BICO input,

however, requires a float value.

–

0x84

Parameter %s [%s]: parameter

change inhibited

(refer to p0300, p0400, p0922)

–

–

0x85

Parameter %s [%s]: access method

not defined.

–

–

0xC8

Below the valid values.

Modification request for a value that, although within

"absolute" limits, is below the currently valid lower limit.

–

0xC9

Above the valid values.

Modification request for a value that, although within

"absolute" limits, is below the currently valid lower limit

(e.g. governed by the current converter rating).

–

0xCC

Write access not permitted.

Write access is not permitted because an access key is

not available.

–