Communication PROFIBUS DP/PROFINET IO

10.2 Communication via PROFIBUS DP

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

415

Field

Value

No. of elements

1

Decimal places

Any

Note
•

You can operate a SIMATIC HMI together with a drive unit independently of an existing

control.

A basic "point-to-point" connection can only be established between two nodes (devices).

•

The "variable" HMI functions can be used for drive units. Other functions cannot be used

(e.g. "messages" or "recipes").

•

Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot

be accessed.

10.2.2.5 Monitoring: telegram failure

Description

After a telegram failure and a monitoring time has elapsed (t_An), bit r2043.0 is set to "1"

and alarm A01920 is output. Binector output r2043.0 can be used for an emergency stop, for

example.
After a delay time has elapsed (p2044), fault F01910 is output. Fault F01910 triggers fault

response OFF2 (pulse inhibit) for the supply and fault response OFF3 (emergency stop) for

SERVO/VECTOR. If no OFF response is to be triggered, the fault response can be

reparameterized accordingly.
Fault F01910 can be acknowledged immediately. The drive can then be operated even

without PROFIBUS.

&\FOLFWHOHJUDPV

IURPPDVWHU

)

W

6 4

5 4

$

U

S

7 

S

7 

Figure 10-27 Monitoring: telegram failure