Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

359

Table 10-7 Description of E_CTW1 (control word for INFEED)

Bit

Meaning

Comments

BICO

0/1

ON

Pulse enable possible

0

ON/OFF1

0

OFF1

Reduce DC link voltage via ramp (p3566), pulse

inhibit/line contactor open

BI: p0840

1

No OFF2

Enable possible

OFF2

0

OFF2

Immediate pulse cancellation and power-on

inhibit

BI: p0844

1

Note:

Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.

2

Reserved

-

-

-

1

Enable operation

Pulse enable is present

3

Enable operation

0

Disable operation

Pulse inhibit is present

BI: p0852

4

Reserved

-

-

-

1

Inhibit motor operation

Motoring operation as step-up converter is

inhibited.

Inhibit motor operation

0

Enable motor operation

Motoring operation as step-up converter is

enabled.

BI: p3532

5

Note:

When "Inhibit motoring operation" is present, power can still be drawn from the DC link. The DC link voltage is then

no longer controlled. The voltage level is the same as the rectified value of the current line voltage.

1

Inhibit regenerative operation

Regenerative operation is inhibited.

Inhibit regenerating

0

Enable regenerative operation

Regenerative operation is enabled.

BI: p3533

6

Note:

If regenerative operation is inhibited and power is fed to the DC link (e.g. by braking the motor), the DC link voltage

increases (F30002).
Acknowledge error

0/1

Acknowledge error

BI: p2103

7

Note:

Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.

8

Reserved

-

-

-

9

Reserved

-

-

-

1

Control via PLC

This signal must be set so that the process data

transferred via PROFIdrive is accepted and

becomes effective.

10

Master ctrl by PLC

0

No control via PLC

Process data transferred via PROFIdrive is

rejected - i.e. it is assumed to be zero.

BI: p0854