Function modules
7.9 Basic positioner
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
255
With position tracking it is recommended to change p0412 or p2721.
Function diagrams (see SINAMICS S List Manual)
● 3635 Interpolator
● 4010 Position actual value conditioning
Overview of key parameters (see SINAMICS S List Manual)
● p2576 EPOS modulo offset, modulo range
● p2577 BI: EPOS modulo offset activation
● p2583 EPOS backlash compensation
● r2684 CO/BO: EPOS status word 2
● r2685 CO: EPOS correction value
Commissioning with STARTER
In STARTER, the mechanical system screen form can be found under position control.
7.9.2
Limits
Description
The velocity, acceleration and deceleration can be limited and the software limit switches
and stop cams set.
Features
● Traversing profile limits
– Maximum velocity (p2571)
– Maximum acceleration (p2572) / maximum deceleration (p2573)
● Traversing range limits
– Software limit switch (p2578, p2579, p2580, p2581, p2582)
– STOP cams (p2568, p2569, p2570)
● Jerk limitation
– Jerk limitation (p2574)
– Activation of jerk limitation (p2575)
Maximum velocity
The maximum velocity of an axis is defined using parameter p2571. The velocity should not
be set to be greater than the maximum speeds in r1084 and r1087.