Vector control

4.12 Motor data identification and rotating measurement

Drive Functions

144

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

DANGER

During speed controller optimization, the drive triggers movements in the motor that can

reach the maximum motor speed. The emergency STOP functions must be fully

operational during commissioning. To protect the machines and personnel, the relevant

safety regulations must be observed.

Note
If speed control optimization is used for operation with encoder, then the control operating

mode is automatically reset to speed control without encoder, so that the encoder test

can be carried out.

Overview of key parameters (see SINAMICS S List Manual)

● r0047 Status identification
● p1300[0...n] Open-loop/closed-loop control operating mode
● p1900 Motor data identification and rotating measurement
● r3925 Identification completion display
● r3927 MotId control word
● r3928 Rotating measurement configuration

Rotating measurement

● p0391 Current controller adaptation starting point Kp
● p0392 Current controller adaptation starting point Kp adapted
● p0393 Current controller adaptation P gain scaling
● p1959 Speed controller optimization configuration
● p1960 Rotating measurement selection
● p1961 Saturation characteristic speed for calculation
● p1965 Speed controller optimization speed
● p1967 Speed controller optimization dynamics factor
● r1968 Speed controller optimization dynamic factor current
● r1969 Speed controller optimization inertia identified
● r1973 Speed controller optimization encoder test pulse number determined
● p1980 Pole position identification technique
● p1990 Encoder adjustment selection

Motor data identification at standstill

● p1909[0...n] Motor data identification control word
● p1910 Motor data identification selection