Basic information about the drive system

12.4 BICO technology: interconnecting signals

Drive Functions

478

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Note
Each installed drive object is allocated a number between 0 and 63 during initial

commissioning for unique identification.

Overview of key parameters (see SINAMICS S List Manual)

Adjustable parameters
● p0101 Drive object numbers
● p0107 Drive object type
● p0108 Drive object configuration
Display parameters
● r0102 Number of drive objects

12.4

BICO technology: interconnecting signals

12.4.1

Description

Description

Every drive contains a large number of interconnectable input and output variables and

internal control variables.
BICO technology (Binector Connector Technology) allows the drive to be adapted to a wide

variety of conditions.
Digital and analog signals, which can be interconnected as required by means of BICO

parameters, are identified by the prefix BI, BO, CI, or CO in their parameter name.
These parameters are identified accordingly in the parameter list or in the function diagrams.

Note
The STARTER parameterization and commissioning tool is recommended when using BICO

technology.

12.4.2

Binectors, connectors

Binectors, BI: Binector Input, BO: Binector Output

A binector is a digital (binary) signal without a unit which can assume the value 0 or 1.